CHS-HY-102D (R3) is a scanner type, stationed, on-line, multi-channel standalone device.
-
It can derive inputs from up to 8 pick-ups either CHS-HTR-PH-100-5V-CM or H2 SENSE-1205.
-
It features alarms, voltage free contacts and a three digit LED display for read-out in terms of percentage Hydrogen in air.
-
It is optionally provided with serial Port RS 232 for continuous data log.
-
This product is installed remote in safe areas.
SPECIFICATIONS OF MULTICHANNEL HYDROGEN DISPLAY MONITOR: CHS-HY-102D (R3)
|
1
|
Type
|
Stationed, environmental, on-line, multichannel, ambient air monitoring, microcontroller based standalone device with recording feature
|
2
|
Input Power Supply
|
Universal – 110V to 260V AC or 120V to 370V DC
|
3
|
Output Power Supply
|
24V DC or 12V DC for input device
|
4
|
Range
|
0-5% H2 in air
|
5
|
Resolution
|
0.01%
|
6
|
Contact
|
Common voltage free relay contact, 2 sets (back panel), NO/NC for two select points
|
7
|
Display
|
3 digit concentration display, channel indicators (1-8) visual alarm LEDs x 2 x 8, for each stage (separate for each channel)
|
8
|
Scan
|
Auto (1-30 seconds) settable, multi-function key pad
|
9
|
Alarm Set
|
High and extra high respectively and independently settable for each channel. Multi-function key pad
|
10
|
Alarm Reset
|
Auto
|
11
|
Accuracy
|
±10% FSD
|
12
|
Mounting
|
Panel/wall mounted in remote safe area, up to 30 meters.
Customized option for distances > 30mts.
|
13
|
Cable Recommended
|
Sensor input cord, four core coaxial shielded.
|
14
|
Input Receptacle
|
4 pin round connector (Female)
|
15
|
PC Interface
|
Standard RS-232 port (3 wire), Baud rate 2400, 8N1.
|
16
|
Accessories
|
2 nos. 4-pin round connector (Male)
|
Specification subject to changes without prior notice, due to continuous R&D and development of Company’s Products
|